Product info
The Doorina board controls a DC brush motor in an electronic door operator. It receives commands from the control panel and manages opening and closing with two independent speed profiles, configured from three buttons and two on-board displays.
Commands can be handled digitally (always on) or over the proprietary serial CAN bus. Two board versions cover 24 V and 48/60 V door operators.
Connectors & wiring
- Motor connector — if the first movement runs the wrong way, reverse the two wires.
- Commands (activated by closing to Common): Common, Limit Close, Limit Open, Close, Open, Nudge.
- Encoder input: +5 V, GND, A+, A-, B+, B- (line-driver) or +5 V, GND, A, B (push-pull).
- CAN-Bus: CAN-L, DGND, CAN-H, VCC.
- RS232 serial port (TX / RX / PGND).
- Relay outputs FCA, FCC, CM, AUX — programmable normally-open or normally-closed.
- Power supply 12/24 VDC.
Operating modes
Select the type of operation with parameters 33, 34 and 35:
- Encoder (par. 33): quadrature (A & B phases) or single phase A.
- Limits (par. 34): slowdown limits, or opening/closing end limits, normally open or closed.
- Times (par. 35): time-based operation when no encoder or limits are available.
Encoder or Times can be combined with end limits, which then become the confirmation points for end-of-open and end-of-close.
Self-learning & speed profiles
The board needs a self-learning cycle to learn the open/closed positions and the maximum speed. Close the doors manually first, then start it from the on-board menu.
During self-learning the board opens and closes at the constant voltage of parameter 37, measures the encoder pulses (or the limit/time states) and sets the speed and ramp parameters automatically. On every power-up it synchronises with a slow closing. Two speed profiles (opening and closing) are then shaped with the numbered parameters.
Safety — obstruction & photocell
- Obstruction contact: when the closing current exceeds the safety threshold (par. 27) for more than ¼ second, closing is interrupted. In master mode the doors reopen automatically; in slave mode the board waits for a command.
- Virtual obstruction (times + limits, par. 66): if the close limit is not seen within the set time, an obstruction is assumed.
- Photocell (encoder mode): shares the 'Limit Close' input; when triggered, closing is interrupted like an obstruction.
Faults & diagnostics
01Encoder not workingCritical
The encoder count does not increase or decrease.
02Motor overcurrentCritical
Motor current above the limit for more than 7 seconds.
03Open & close togetherWarning
OPEN and CLOSE inputs activated at the same time.
04EEPROM read errorWarning
Failed to read parameters from EEPROM.
05EEPROM write errorWarning
Failed to save parameters to EEPROM.
06Bus voltage too lowCritical
DC bus voltage too low.
Remedy: Check the 24 V input and the on-board fuse.
07Self-learning failedWarning
Self-learning did not complete correctly.
08Encoder direction wrongWarning
Encoder rotation direction is reversed.
Remedy: Change parameter 39 or 58.
09Obstruction on closingWarning
Obstruction contact tripped while closing.
12Door not closed in 30 sWarning
The door did not close within 30 seconds.
13Door not opened in 30 sWarning
The door did not open within 30 seconds.
15Limits fault on openingWarning
Opening/closing limits detected in a failure state during opening.
Remedy: Check parameter 34.
16Limits fault on closingWarning
Opening/closing limits detected in a failure state during closing.
Remedy: Check parameter 34.
17Obstruction on openingWarning
Obstruction current or contact tripped while opening.
18Both limits activeWarning
Opening and closing limits both active — inconsistent.
Remedy: Check parameter 34.
19Self-learning timeoutWarning
Timed out during self-learning.
20Self-learning values inconsistentWarning
Self-learning produced inconsistent values.
21No current in self-learningCritical
No motor current during self-learning.
Remedy: Check the motor connection.
22Closing timeout at startWarning
Timed out closing the door at start-up.
23Photocell tripped on closingInfo
The photocell intervened during the closing phase.
26Command interrupted earlyInfo
Command interrupted before an actual opening or closing.
27Virtual obstruction contactInfo
The 'virtual' obstruction contact intervened.
30No CAN communicationCritical
No CAN bus communication for more than 3 seconds.